Micro-OPLC Installation Guide 6 Digital, 2 Analog/Digital, 2 Analog Inputs, 6 Relay Outputs
Before using this product, the user must read and understand this document. For additional information regarding this product, refer to the user guide and technical specifications. All examples and diagrams are intended to aid understanding, and do not guarantee operation. Unitronics accepts no responsibility for actual use of this product based on these examples. Please dispose of this product according to local and national standards and regulations. Only qualified service personnel should open this device or carry out repairs. Failure to comply with appropriate safety guidelines can cause severe injury or property damage. Do not attempt to use this device with parameters that exceed permissible levels. To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
Do not install in areas with: excessive or conductive dust, corrosive or flammable gas, moisture or rain, excessive heat, regular impact shocks or excessive vibration. Ventilation: 10mm space required between the OPLCs’ top/bottom edges & enclosure walls. Do not place in water or let water leak onto the unit. Do not allow debris to fall inside the unit during installation.
Mounting
Dimensions
147.5 mm (5.807") 12 mm (0.472") 16.8 mm (0.661")
4 mm (0.157")
7.5 mm (0.295")
85.7 mm (3.374")
117 mm (4.606")
46.6 mm (1.835")
13.2 mm (0.52")
113.7 mm (4.476")
Add-on modules Take into account that installing an add-on module requires sufficient clearance space. During installation
72 mm (2.835")
27.5 mm (1.083")
After installation
Unitronics
35.8 mm 38 mm (1.409") (1.496")
1
2/06
JZ10-11-R16
DIN-rail mounting Snap PLC onto the DIN rail
Panel mounting Cut-out: 117 x 89mm (WxH) 4.606”x 3.504”
Panel 5mm (max) 0.197" (max)
. .
53 mm (2.087")
35 mm (1.378")
Gasket
Wiring
Note: All